Download this standard in MS Word 2000 format (200Kb)

EUROPEAN STANDARD EN 50107

 

Signs and luminous-discharge-tube installations operating from a no-load rated output voltage exceeding 1000 V but not exceeding 10000 V.

 

1.       SCOPE

This European Standard specifies the requirements and method of installation for signs and luminous-discharge-tube installations operating from a no-load rated output voltage exceeding 1000V but not exceeding 10000V, including the electrical components and wiring.

The standard covers inatallations used for publicity, decorative or general lighting purposes, either for external or internal use. Such signs or luminous-discharge-tube installations may be either fixed or portable supplied from a low-voltage (L.V) or extra-low-voltage (E.L.V) source by means of a transformer, invertor or convertor.

Although the requirements are not specified in this Standard, attention is drawn to the need for an effective maintenance programme to be carried out on all signs or luminous-discharge-tube installations. The inspection and testing requirements included in any maintenance programme should closely follow those specified in Clause 18 of this Standard.

2.       NORMATIVE REFERENCES

This European Standard incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to the European Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies.

EN50143 - Cables for signs and luminous-discharge-tube installations operating from a no-load rated output voltage exceeding 1 000 V but not exceeding 10 000 V.

EN 55015 - Limits and methods of measurement of radio interference characteristics of fluorescent lamps and luminaries.

EN 60529 - Degrees of protection provided by enclosures (IP Code).

EN 61000 - Electromagnetic compatibility (EMC). Part 3, Limits. Section 2, Limits for harmonic current emissions (equipment input current not exceeding 16 A/phase).

EN 60598–1 - Luminaries: Part 1, General requirements and tests.

EN 61050 - Transformers for tubular discharge lamps having a no-load output voltage exceeding 1 000 V (generally called neon-transformers). General and safety requirements.

HD 384 - Electrical installations of buildings.

ISO 3864 - Safety colours and safety signs.

3.       DEFINITIONS

For the purposes of this European Standard, the definitions given in IEC 50 (IEV) apply, together with the following.

Note: Where the terms 'voltage' and 'current' are used, they imply the r.m.s. values unless otherwise specified.

3.1.      luminous-discharge tube: Any tube, or other vessel or device, which is constructed of translucent material, hermetically sealed, and designed for the emission of light arising from the passage of an electric current through a gas or vapour contained within it.

Note: The tube may be with or without a fluorescent coating.

3.2.      no-load rated output voltage: Maximum rated Voltage between the terminals of the output winding(s) of the transformer connected to the rated supply voltage at rated frequency, with no load on the output circuit. It is the peak value divided by the square root of 2.

3.3.      creepage distance: The shortest path between two conductive parts or between a conductive part and the bounding surface of the installation, measured along the surface of the insulating material.

Note: The bounding surface of the installation is the inner surface of the enclosure, considered as though a metal foil were pressed into contact with all interior surfaces of insulating material.

3.4.      clearance: The shortest distance between two conductive parts or between a conductive part and the bounding surface of the installation, measured through the air.

Note: See note to 3.3.

3.5.      transformer: A unit for the conversion of an a.c. supply at one voltage and frequency to an a.c. supply at a different voltage and the same frequency.

Note: The high output impedance of most transformers designed for cold-cathode discharge tubes allows the characteristics of transformer and current-limiting components to be combined in one unit.

3.6.      invertor: An electric energy transducer that converts direct current to alternating current.

3.7.      convertor: A unit for the electronic conversion of an a.c. supply at one frequency to an a.c. supply at another frequency.

Note: The voltage may or may not be altered during the conversion.

3.8.      insulating sleeve: Insulation designed to be placed over the exposed high-voltage connections at tube electrodes or over cable-end insulator.

3.9.      Installer: The person, qualified in sign installation practice, who takes responsibility for the installation and its testing in accordance with this standard.

3.10.   earth-leakage protective device: A device which will remove the output. power from a transformer(s), invertor(s) or convertor(s) in the event of a short circuit between any part of the secondary high voltage circuit and earth.

Note: The device may be in two parts, a sensor and a protective switch (see 3.12 and 3.13), or may be combined in one unit.

3.11.   open-circuit protective device: A device which will remove the output power from a transformer(s), invertor(s) or convertor(s) in the event of an interruption of the secondary high voltage circuit.

Note: The device may be in two parts, a sensor and a protective switch (see 3.12 and 3.13), or may be combined in one unit.

3.12.   sensor: That part of a protective device which detects the presence of a secondary earth fault and/or an open circuit condition and provides a signal to operate a protective switch.

3.13.   protective switch: That part of a protective device which disconnects the mains supply to a transformer(s), invertor(s) or convertor(s) or otherwise removes the output power. It is operated by an electrical signal obtained from a sensor. 

3.14.   live part: A conductor or conductive part intended to be energised in normal use, including the neutral conductor but, by convention, not a PEN conductor. 

3.15.   input end (low-voltage circuit): The part of the device between the point at which electrical energy is supplied to an installation and the input terminals of the transformer, convertor or invertor. 

3.16.   output end (lamp circuit): The part of the device between the output terminals of the transformer, convertor or invertor and the discharge tubes inclusive. 

3.17.   arm's reach: A zone extending from any point on a surface where persons usually stand or move about to the limits which a person can reach with the hand in any direction without assistance. 

Note: This zone of accessibility is shown in figure 1 in which the values refer to bare hands without any assistance, e.g. from tools or from a ladder. 

3.18.   outdoor sites: Sites where all or part of a sign or luminous-discharge-tube installation or its components are situated out of doors and are subject to the effects of weather. 

3.19.   dry rooms and places: Rooms ox places where condensation does not usually occur or the air is not saturated with moisture.

3.20.   damp and wet rooms and places: Rooms or places where the safety of the sign ox' luminous-discharge-tube installation may be affected by humidity, condensation, chemical or similar influences.

3.21.   small portable signs: Small signs which can easily be moved from one place to another; which are supplied with an integral transformer, invertor or convertor, together with a flexible mains supply lead and plug; and which are intended to be installed and connected by the customer to a socket outlet of the mains supply. 

3.22.   flasher: A device for automatically switching one or more lamp circuits on and off continuously. The sequence of switching of the various lamp circuits may be suitably arranged to provide the impression of movement and other animated effects.

4.       MEANS OF ATTACHMENT OF SIGNS

Electrical conductors shall not be used as means of suspension or attachment of signs. 

5.       DRAIN HOLES

In sign enclosures intended for external use, arrangements shall be made to allow moisture to drain away. Drain holes or similar apertures used for this purpose shall be sufficiently large to ensure that they do not become blocked with dirt or debris between maintenance visits.

6.       INSTALLATION OF THE MAINS SUPPLY

Installation of the mains supply for signs and luminous - discharge-tube installations shall be carried out in accordance with HD 384. 

Note: Attention is drawn to the fact that wiring rules are not fully harmonised in CENELEC countries and, for this reason, national standards apply. 

7.       ENCLOSURES AND PROTECTION OF LIVE PARTS

7.1.      All high-voltage connections to discharge tubes shall be protected by means of insulating sleeves conforming to clause 13. 

7.2.      High-voltage connections situated within arm's reach shall have additional protection conforming to 7.4 and 7.5.

Note: The description of arm's reach is shown in figure l. 

7.3.      High-voltage connections situated out of arm's reach shall have additional protection conforming to 7.4 or 7.6. 

7.4.      Additional protection shall consist of an enclosure or other means of protection conforming to the following:

a)     It shall provide a degree of protection corresponding to at least IP 2X in Table 1 of EN 60529.

Note 1: The requirements for protection against ingress of solid objects, specified in Table 2 of EN 60529,do not apply.

b)     If it is constructed from metal parts, these shall be earthed in accordance with   clause 8. 

c)     If it is constructed from other materials, these shall be certified by the supplier as suitable for use in the environment existing close to a tube electrode. The materials shall be guaranteed by the supplier for the expected lifetime of the installation. 

Note 2: Suppliers of such materials should be informed of the temperature, ultraviolet (UV) radiation, ozone and other conditions existing near a tube electrode. They should also be informed that such materials may be used in exterior situations. 

d)     Access to the interior of an enclosure shall be by means of a tool, e.g. a screwdriver. 

Note 3: Other means of additional protection may be permanent., e.g. it may have to be cut away using a knife. 

Note 4: A fully-enclosed sign letter or box sign is considered to be a suitable enclosure for this purpose.

7.5.      Additional protection shall consist of either:

a)     An enclosure as specified in 7.4 where the degree of protection (IP 2X) is maintained even if any external parts of a tube are broken; or

b)     the circuit shall be provided with open-circuit protection complying with the requirements of 10.6. This being in addition to the mechanical enclosure specified in 7.4. 

Note: The requirement of 7.5(a) means that it is not possible to insert the appropriate test finger into the broken end of a tube and touch a live electrode. 

7.6.      Additional protection shall consist of open-circuit protection complying with the requirements of 10.6.

7.7.      Symbols for 'caution, risk of electric shock' conforming to B.3.6 of ISO 3864: 1984 shall be fixed at points of access to any sign, luminous-discharge-tube installation or enclosure containing high-voltage transformers, invertors or convertors. The length of side of the triangle enclosing the symbol shall be not less than 50 mm.

Note: In small installations of limited extent, one such symbol should normally be adequate. More than one symbol should be used for larger installations and these should be arranged so that at least one is visible from any likely direction of approach to the installation.

7.8.      A conductor which is in metallic contact with a discharge tube operating at high voltage shall not be in connection (except in respect of its connection to earth) with any other conductor of the mains supply or with the primary winding of the transformer.

7.9.      Creepage distances and clearances in millimetres between live parts carrying different voltage supplies, between live parts and earthed metalwork or between live parts and parts which may become conductive when wet or are flammable shall be as follows.

a)     for equipment which is installed in dry rooms and similar protected situations: shortest creepage distance: d = 8 + 4U; shortest clearance: c = 6 + 3U;

b)     for equipment which is installed outdoors or in damp or wet rooms:                  shortest creepage distance: d = 10 + 5U; shortest clearance: c = 7,5 + 3,75U;

c)     for equipment operating at. frequencies greater than 1 kHz, whether this is installed in dry or damp situations:                                                                                                   shortest creepage distance: d = 12 + 6U; shortest clearance: c = 9 + 4,5U;

where:
U is the rated no-load output voltage of the transformer, invertor or convertor supplying the circuit in kilovolts. 

8.       PROTECTION AGAINST INDIRECT CONTACT

8.1.      The protection against indirect contacts shall be provided by an equip-potential bonding, generalised between all metal parts and then connected to earth.

8.2.      All exposed metalwork with the exception of clips and clomps for fixing cables and tubes, shall be bonded together by means of a protective conductor and, unless this metalwork is connected to earth by other means, shall be provided with an earthing terminal. 

8.3.      The protective conductor shall be one of the following: 

a)     a separate cable having insulation coloured yellow/green and having the following cross-sectional area:

i)                in situations where it may suffer mechanical stress, 4 mm2;

ii)              in other situations, 2,5 mm2 ; or 

b)     a stranded or solid copper conductor having a minimum cross-sectional area of not less than 1,5 mm2, Manufacturerd as part of a sheathed high-tension cable and protected by the overall sheath of that cable; or

c)     the braided metal screen of a high-voltage cable, provided that the total cross-sectional area of the individual  strands comprising that screen is not less than 1,5 mm2. Connections to the screen shall be made by unravelling the braid and twisting the individual strands together to form a suitable length of conductor to attach to an earth terminal. The connection shall not be by means of a metal clamp around the braid. 

8.4.      Where adhesive is used between metal parts, or where painted metal parts are bolted or screwed together, unless a bonding conductor is connected between the parts, means shall be employed to ensure that earth continuity is maintained across the joint.

8.5.      Equipotential bonding conductors shall not be connected to the neutral terminal of the mains supply to the sign or luminous-discharge-tube installation, except as specified in HD 384 for protective multiple earthing arrangements in TN-C systems.

9.       TRANSFORMERS

Transformers shall conform to EN 61050 except that the no-load rated output voltage shall not exceed 5 kV to earth or exceed 10 kV between terminals. 

10.    EARTH-LEAKAGE AND OPEN-CIRCUIT PROTECTION 

10.1.   The requirements for earth-leakage protection are specified in 10.2 to 10.5. Those for open-circuit protection are specified in 10.6 to 10.9- The requirements in 10.10 to 10.15 apply to both types of protection.

10.2.   High-voltage circuits supplied from transformers, invertors or convertors shall be protected by an earth-leakage protective device conforming to 10.3 and 10.4. The installer shall ensure that performance of the earth-leakage protective device is certified by the Manufacturer of the device as conforming to 10.5.

10.3.   In the event of accidental contact between the high-voltage circuit and earth, the earth-leakage protective device shall either disconnect the mains supply to the input circuit, or otherwise remove  the output power. If single-pole mains-supply switching is provided, the switch shall be connected in the phase lead of that supply.

Note: A standard residual-current-operated circuit-breaker is not a suitable protective device for this application since, when connected to the primary side of a transformer, invertor or convertor,  it does not protect against faults to earth on the secondary side. 

10.4.   Detection of a fault condition shall be made by means of suitable sensor(s) connected in the output circuit(s), or other suitable means, and these shall either operate switches to disconnect the mains supply to the input circuit or otherwise remove the output power.

Note 1: The sensors and switches for the device may be combined into one unit. 

Note 2: Earth-leakage protective devices may be designed to protect more than one sign circuit. 

10.5.   The earth-leakage protective  device shall conform to the following. 

a)     If the sensor and/or the protective device to remove the output power is mounted in a position not within the case of the transformer, invertor or convertor, it shall operate correctly over  a temperature range - 25 °C to +65 °C.

b)     If any part of the sensor and/or the protective switch or device to remove the output power is mounted within the case of the transformer, invertor or convertor, that part shall operate correctly over the temperature range expected to occur within that case. The installer shall obtain information from The Manufacturer of the transformer, invertor or convertor in order to verify that the maximum operating temperature of that part of the sensor and/or the protective device is not exceeded when the transformer, invertor or convertor is operating at its maximum ambient temperature and under specified abnormal conditions.

c)     The rated operating current shall be less than the earth-leakage current (measured over the expected supply voltage range into a short circuit to earth) of the transformer, invertor or convertor to be protected and shall not exceed 25 mA.

Note: The actual current which flows through the sensor circuit during earth fault is determined by the impedance of that fault path and the output characteristics of the transformer, invertor or convertor feeding the fault. It does not depend on the operating current of the protective device.

d)     The time to operate, at rated current, shall be not more than 200 ms. 

e)     The voltage across that part of a sensor which is detecting the earth-leakage current shall not exceed 50 V. The installer shall obtain information from the Manufacturer of the earth-leakage protective device in order to verify that this voltage shall not be exceeded with the protective switch circuit disconnected and with the highest anticipated fault current.

Note: The highest anticipated fault current is the short circuit current through one half of the output winding of the highest rated current transformer, invertor  or convertor to be protected.

f)      Means shall be provided to facilitate maintenance. Such means shall be accessible only with the aid of a tool and shall be automatically reset when the supply voltage to the earth-leakage protective device is switched off and then switched on again. The installer shall ensure that suitable maintenance procedures are provided by the Manufacturer of the earth-leakage protective device.

g)     The installer shall ensure that suitable test procedures conforming to 18.3(a) are provided by the Manufacturer of the earth-leakage protective device.

10.6.   Where specified in 7.4 and 7.6, high-voltage circuits supplied from transformers, invertors or convertors shall be protected by an open-circuit protective device conforming to 10.7 and 10.8. The installer shall ensure that performance of the open-circuit protective device is certified by the Manufacturer of the device as conforming to 10.9.

10.7.   In the event of an open circuit occurring in the high-voltage circuit., the open-circuit protective device shall either disconnect the mains supply to the input circuit, or otherwise remove the output power. If single-pole mains-supply switching is provided, the switch shall be connected in the phase lead of that supply.

10.8.   Detection of a fault condition shall be made by means of suitable sensor(s) connected in the output circuit(s), or other suitable means, and these shall either operate switches to disconnect the mains supply to the input circuit or otherwise remove the output power.

Note 1: The sensors and switches for the device may be combined into one unit.

Note 2: Open-circuit protective devices may be designed to protect more than one sign circuit.

10.9.   The open-circuit protective device shall conform to the following.

a)     If the sensor and/or the protective device to remove the output power is mounted in a position not within the case of the transformer, invertor or convertor, it shall operate correctly over a temperature range -25 °C to +65 °C.

b)     If any part of the sensor and/or the protective switch or device to remove the output power is mounted within the case of the transformer, invertor or convertor, that part shall operate correctly over the temperature range expected to occur within that case. The installer shall obtain information from the Manufacturer of the transformer, invertor or convertor in order to verify that the maximum operating temperature of that part of the sensor and/or the protective device is not exceeded when the transformer, invertor or convertor is operating at its maximum ambient temperature and under specified abnormal conditions. 

c)     If the installation is switched on with an open-circuit condition existing in any part of the output circuit or tube load, the protective device  shall operate in a time of not less than 3 seconds and not more than 5 seconds. 

Note: Attention is drawn to the fact that certain types of transformer having a semi-resonant capacitive output characteristic are capable of operating greater tube loads than can be accommodated on transformers having similar output voltages,  but with the normal inductive output characteristics. However, tubes operated by such transformers may be slow to start, particularly at low temperatures. If starting is delayed too much, it may give rise to spurious tripping of open-circuit protective devices. 

d)     If an open circuit occurs in any part of the output circuit or tube load whilst the installation is switched on, the protective device shall operate in a time not exceeding 200 ms. If the mains supply is then switched off and switched on again, with the open-circuit condition still persisting, the device shall operate in a time of not less than 3 seconds and not more than 5 seconds.

e)     Means shall be provided to facilitate maintenance. Such means shall be accessible only with the aid of a tool and shall be automatically reset when the supply voltage to the open-circuit protective device is switched off and then switched on again- The installer shall ensure that suitable maintenance procedures are provided by the Manufacturer of the open-circuit protective device.

f)      The installer shall ensure that suitable test procedures conforming to 18.3(a) are provided by the Manufacturer of the open-circuit protective device.

10.10.    The sensor (or sensors) shall be connected to the earth-leakage or open-circuit protective device to remove the output power by either:

a)     connecting each sensor to its own device, which may or may not be incorporated within the housing of the transformer, invertor or convertor; or

b)     connecting the sensors of a number of transformers, invertors or convertors to a single protective device which is connected in the mains supply to their input circuit. The number of sensors which may be connected to one protective device shall be in accordance with the instructions of the Manufacturer of the protective device. 

10.11.    If the protective device is arranged to disconnect the mains supply in the event of an earth fault or open circuit, the means to do this shall use mechanical contacts. The use of semiconductor switches (thyristors, triacs, etc.) shall not be permitted except where invertors or convertors provide galvanic isolation between input and output. In this case the output voltage may be removed by electronic means, e.g. disablement of the oscillator circuit.

10.12.    After a secondary earth fault or open circuit has caused the protective device to operate, it shall remain as it is until the mains supply is also switched off. When the mains supply is switched on again, the protective device to remove the output voltage shall automatically reset. If the earth-leakage or open-circuit fault is still present at the time of the reset, the protective device shall operate in accordance with 10.5 or 10.9 as appropriate.

Note: This requirement ensures that spurious tripping, caused by the presence of rain water or condensation or possible brief periods of extra slow starting is cleared on the next switching of the mains supply. 

10.13.    If the circuit includes a flasher, any protective switch and its reset circuit shall be installed on the mains-supply side of the flasher.

Note: If they were on the other side of the flasher, the switch would keep re-setting and re-tripping during fault conditions.

10.14.    If the circuit includes a flasher and the device(s) to remove the output power is incorporated within the housing of the transformer(s), invertor(s) or convertor(s), a protective switch shall be connected on the mains-supply side of the flasher and the incorporated sensor circuits shall be capable of operating this second switch. 

10.15.    Sensors and protective devices shall be compatible with each other.

11.    INVERTORS AND CONVERTORS

Note: The requirements for invertors and convertors for neon tubes will be discussed by a panel to be convened by WG-COMEX. This panel will produce a draft specification         IEC 1347, Part 2.11. When this standard is issued, its requirements will replace those of      Clause 11. 

11.1.   The installer shall ensure that invertors and convertors are suitable for their intended application in respect of:

a)     supply voltage, or voltage range;

b)     input current or input power;

c)     input and output frequencies;

d)     no-load output voltage, including tolerance (see 11.2);

e)     rated output current and current range;

f)      earth connections to the output circuit (see 11.3).

Note: Invertors and convertors provide a high-frequency, high-voltage output. The effects of high frequency supplies on the insulation and operation of circuits and components should be carefully considered.

11.2.   Invertors and convertors shall have an open-circuit voltage to earth, at rated supply voltage and frequency, not exceeding 5 kV, this voltage being either the r.m.s. value or 0,5 times the peak value, whichever is the greater. The tolerance on this voltage shall be -0/+10 %. The installer shall obtain information about the output voltage from the Manufacturer of the invertor or convertor.

11.3.   Invertors and convertors shall have one point on the output circuit. connected to earth and there shall be no direct connection between any output terminal and either mains supply terminal. 

11.4.   Invertors and convertors shall be installed in accordance with the instructions of the Manufacturer. 

11.5.   The length and type of cable connecting the high-voltage terminal of an invertor or convertor to a discharge tube shall not exceed that specified by the Manufacturer. 

12.    AUXILIARIES

Independent auxiliaries for signs and luminous-discharge-tube installations operating at high voltage, such as inductors, capacitors and resistors, shall be protected by being placed within an enclosure conforming to clause 7.

13.    INSULATING SLEEVES

13.1.   Insulating sleeves, used for the protection of electrodes and the connections, shall be made from one of the following:

a)     glass having a minimum wall thickness of 1 mm, or

b)     high-tear silicone rubber, with a Shore hardness of 50 +/ - 5, a minimum wall thickness of 1 mm and an operating temperature of at least 180 °C, or

c)     material with insulating, resistance to UV radiation and ozone and heat-resistance characteristics at least equivalent to those given in item (b).

14.    SPECIFICATION AND INSTALLATION OF HIGH-VOLTAGE CABLES

14.1.   The high-voltage cables used shall be selected, as appropriate, from the list of cables conforming to EN50143, given in annex A.

14.2.   All cables shall be suitable for the environmental conditions expected in the sign or luminous-discharge-tube installation.

14.3.   Cable type 'K' shall be used only for continuous operation at voltages up to 2,5 kV to earth.

Note: Cables type 'A' to 'H' may be used for continuous operation at voltages up to 5 kV to earth. 

14.4.   Provided they are not likely to suffer mechanical damage, cables shall be used without further mechanical protection in accordance with the requirements of Table 1.

Table 1. Installation requirements for cables complying with EN50143 

 

Cables may be used for installations:

Cable type

 

within protective enclosures

in all situations other than in or under surfaces

in or under surfaces

A

X

X

X

B

X

-

-

C

X

X

-

D

X

X

X

E

X

X

X

F

X

X

-

G

X

-

-

H

X

X

-

K

X

X

-

Note 1: The cable insulation may be allowed to come into contact with earthed metalwork or other materials within an enclosure.

Note 2: Examples of protective enclosures include sign boxes, enclosed letters, cable ducting, steel tubes and flexible armoured conduit.

14.5.   Cables installed in situations where mechanical damage is likely shall be protected by trunking or similar means, constructed either of earthed metal or from a low-flammability material having self-extinguishing characteristics as defined in 13.3 of EN 60 598-1: 1993.

14.6.   Cable type 'A' shall not be drawn into conduits or other restricted enclosures, other than short lengths, such as may exist through walls and floors. If these short lengths of conduit are made of metal, they shall be earthed.

14.7.   Except where temporary connections are made to complete a high-voltage circuit when a tube is removed for repair, high-voltage cables shall be continuous and no joints shall be permitted.

14.8.   The length of the high-voltage cable shall be as short as practicable. 

Note: This requirement is particularly critical for cables having an earthed metal screen. The self-capacitance between the cable conductor and its metal screen may cause short-duration high-amplitude current peaks to occur through the tube. Such peaks are particularly troublesome with discharge tubes filled with neon and can lead to radio interference problems, flicker and short tube lives. Table 2 shows recommended maximum cable lengths for neon or mercury tubes connected by screened or unscreened cables to transformers operating at a frequency of 50 Hz. The maximum lengths are related to the transformer no-load output voltage to earth.

Caution. This table is provided for guidance only. It is not guaranteed to ensure correct operation for all operating currents and tube diameters.

Table 2: Recommended limiting values for simple wiring length

Voltage to earth

1 kV

2 kV

3 kV

4kV

5kV

Type of gas inside tube

Hg

Ne

Hg

Ne

Hg

Ne

Hg

Ne

Hg

Ne

Cable type B,C,F,G,H,J (in metres)

40

20

30

15

20

10

15

7

10

5

Cable type A,D,E (in metres)

24

12

16

8

12

6

9

4

6

3

14.9.   The cable between the output terminals of an invertor or convertor and the discharge tube shall be of a type specified by the Manufacturer and shall:

a)     be suitable for operation at high frequency; and

b)     be suitable for operation at the output voltage of the invertor or convertor.

14.10.    Where transformers, invertots or convertors have only one high-voltage terminal, the cable between the discharge tube and the earth, or return, terminal of the transformer, invertor or convertor shall conform to 14.1 to 14.9.

14.11.    Supports for cables shall be of metal or non-hygroscopic material having 8elf extinguishing characteristics as defined in 13.3 of EN 60 598 - 1: 1993.

14.12.    The distance between supports for cables and conductors shall not be greater than the appropriate value given in table 3.

Table 3: Distance between cable and conductor supports

Type of cable or conductor

Distance between supports for cable or conductors with an angle to the horizontal

 

up to 45°

over 45 °

Cables having a flexible conductor

500 mm

800 mm

Cables having a solid conductor

800 mm

1250 mm

14.13.    The first support of a cable shall be at a distance no greater than 150 mm from the terminal to which it is connected.

14.14.    Cables with metal screens shall not be formed into a radius less than eight times the diameter of the cable.

14.15.    Points of entry of cables into enclosures shall be provided with glands or bushes to protect cables against abrasion and shearing. Where the enclosure is installed out of doors, the gland or bush shall also offer protection to at least IPX4 of EN 60529.

15.    HIGH-VOLTAGE CONNECTIONS

15.1.   Connections to the tube shall be by means of terminals or other suitable means conforming to 15.2 and 15.3.

15.2.   Connections shall be protected against the effects of rusting and other corrosion.

15.3.   The mechanical strength of high voltage connections shall be adequate for all normal service conditions.

15.4.   Cable insulation or a metal screen exposed by the removal of the plastic sheath shall, where necessary, be protected from the effects of weather, UV radiation or ozone.

Note: For guidance, typical arrangements for high-voltage connections are shown in figures 2, 3 and 4.

16.    SUPPORTS FOR LUMINOUS-DISCHARGE TUBES

16.1.   Supports for luminous-discharge tubes shall be insulated from earth to withstand the no-load output voltage of the transformer, invertor or convertor supplying those tubes.

Note: They may be Manufacturerd from metal which is mounted on an insulator or Manufacturerd entirely from insulating material.

16.2.   The creepage distance and clearance between the glass wall of the tube or any metal clip attached to the tube and earthed metalwork, in millimetres, shall not be less than the following:
creepage distance D = U clearance C = 0,75 x U,
where:
U = the no-load output voltage of the transformer, invertor or convertor supplying the equipment, in kilovolts.

16.3.   The insulating material shall not deteriorate when subjected to the UV radiation and ozone present in the vicinity of the tube. It shall have self-extinguishing flammability characteristics as defined in 13.3 of EN 60 598-1: 1993.

Note: Examples of suitable materials include, glass, glazed ceramics and polycarbonates.

16.4.   The supports shall hold the tube securely under normal service conditions without strain or damage to the tube.

Note: Supports should include a means for adjustment to allow for manufacturing tolerance between the discharge tube and its mounting.

17.    ELECTROMAGNETIC COMPATIBILITY

17.1.   Signs and luminous-discharge-tube installations shall conform to the requirements of EN 55015 for the suppression of radio interference and EN 61000-3-2 for limits for harmonic current emissions.

Note: The requirements for radio interference from neon signs are under discussion.

17.2.   Components fitted to comply with 17.1 shall be rated for the voltages and frequencies to which they will be subjected.

18.    INSPECTION AND TESTING OF INSTALLATIONS

18.1.   Except for small portable signs, which are accompanied by a certificate from their Manufacturer, indicating compliance with this Standard, signs or luminous-discharge-tube installations shall be inspected in accordance with 18.2 and tested in accordance with 18.3.

18.2.   When the installation has been completed, the installer shall check that the sign or luminous-discharge-tube installation conforms to this standard.

Note: Particular care should be taken to ensure conformance of the following items:

a)     the types of high-voltage cable used and their installation;

b)     the high-voltage connections;

c)     the creepage distances and clearances;

d)     the earthing connections;

e)     the mechanical details of the sign or luminous-discharge-tube installation necessary to ensure compliance with this Standard.

18.3.   After the inspection of the sign or luminous-discharge-tube installation, specified in 18.2, the following electrical tests shall be made.

a)     Earth-leakage and open-circuit protective devices shall be tested in accordance with the instructions of the supplier of those devices. Such tests shall ensure that the units are functioning properly and have been installed correctly (see 10.5(g) and 10.9(f)).

Note 1: Such tests are not intended to test the performance of the devices. The specification will be certified by the supplier of the device.

b)     Unless operated from a constant-current transformer, invertor or convertor, the tube current in each circuit shall be measured to ensure that it lies within the tolerance specified by the Manufacturer of the transformer, invertor or convertor.

Note 2: This test is preferably carried out at premises where the sign is Manufacturerd and where the particular set of tubes together with their transformer, invertor or convertor can be conveniently assembled on a bench.

19.    MARKING AND SITE RECORDS

19.1.   The following details shall be marked permanently and legibly on a suitable plate or label attached to, or positioned in a clearly visible place close to, the sign or luminous-discharge-tube installation.

a)     the name and address of the sign Manufacturer or company responsible for the installation,

b)     the year of the installation.

19.2.   To assist in the maintenance of the sign or luminous-discharge-tube installation, the sign installer shall supply the sign operator a simplified circuit diagram, data sheet or other means identifying which transformers, invertors or convertors are operating which tubes.

19.3.   The information provided in accordance with 19.2 shall be amended following any maintenance leading to alterations in the circuits of the sign or luminous-discharge-tube installation.


Figure 1:   Zone of Accessibility for the Definition ‘Arm’s Reach’

 


 

 

 

 

 

 




Figure 2:   Example of an Arrangement Within an Internally Illuminated Letter.

 

 

 

 



Figure 3:   Example of an Electrode Housing Passing Through a Fascia Panel.

 

 


 

 

 

 



Figure 4:   Example of an Arrangement of a Surface-Mounted Tube with the Electrode

Passing Through a Metal Panel.

 

 

 

 

 



Annex A (Informative)

List of high-voltage cables specified in EN50143.

Cable type 'A': A rigid, single-core, 85 0C elastomer insulated cable, with a lead-alloy screen and no sheath.

Cable type 'B': A flexible, single-core, 150 0C silicone elastomer insulated cable.

Cable type 'C': A flexible, single-core, 150 0C silicone elastomer insulated cable and sheathed, either with PVC or a polymeric compound having low emission of smoke and poisonous gases when affected by fire.

Cable type 'D': A flexible, single-core, 150 0C silicone elastomer insulated cable, wire-braided and sheathed, either with PVC or a polymeric compound having low emission of smoke and poisonous gases when affected by fire.

Cable type 'E': A flexible, single-core, PVC-insulated cable with a metal zinc tape screen and a flexible protective conductor. The cable has an overall sheath of PVC.

Cable type 'F': A flexible, single-core, PVC-insulated cable with a flexible protective conductor and an overall sheath of PVC.

Cable type 'G': A flexible, single-core, PVC-insulated cable.

Cable type 'H': A flexible, single-core, polyethylene-insulated cable with an overall sheath of PVC. The nominal thickness of the polyethylene insulation is 3 mm.

Cable types 'K': A flexible, single-core, polyethylene-insulated cable with an overall sheath of PVC. The nominal thickness of the polyethylene insulation is 1.5 mm.